Woods 1.6 Speed Controller Fuse

24/11/23

Can you please tell me what causes the fuse in the speed controller to blow? We had the Flaktwoods extractor fan and speed controller replaced last year.

Is the right fuse being used a 10A500V? Could you please tell me the right fuse we should be using? Thanks.


Answer

The fuse is fine to use with this speed controller. Fuses are there to protect life and don’t offer any motor or speed controller protection. In the first instance we would suggest bypassing the speed controller to make sure there’s no fault with the fan, this is one of the main reasons fuses blow in the speed controller or back at the main board, if it is a fan fault we would expect the fuse to blow instantly on start up, we can talk you though the process if required. 

Back To Top

Cookies

We use analytical cookies that need your permission. For more details and advanced options view our Cookies Policy.